This paper describes laboratory experiments on the flow and stratification produced in two coupled rooms connected to the exterior by a single vent. The two rooms are connected by two openings one at high-level and one at low-level in the dividing wall. One ‘forced’ room has a buoyancy source while the outlet vent is in the ‘unforced’ room and is placed in such a way that the buoyancy in the room can potentially drive an exchange flow through it. The buoyancy source is also a source of volume, such as cool air pumped into a room from an overhead duct in which case the outlet is on the floor of the unforced room. We consider the effect of the size of the outlet vent on the resulting stratification in the two rooms. For a small vent only unidirectional flow occurs and, since no ambient fluid enters the rooms, the buoyancy in both rooms becomes uniform and asymptotes to the buoyancy of the source. Above a critical vent size a bidirectional flow is driven through the vent by the buoyancy forces. In this case ambient fluid enters the rooms and a steady state is reached when the buoyancy flux through the outlet vent equals that of the buoyancy source. Both rooms remain stratified with two-layer stratification in this case, with a mean density that decreases as the size of the outlet increases. The implications for ventilation are discussed.
Skip Nav Destination
ANES/ASME Solar Joint 2006 XXXth Mexican National Solar Energy Week Conference
October 2–6, 2006
Puerto de Veracruz, Mexico
Conference Sponsors:
- SE
ISBN:
0-7918-4264-9
PROCEEDINGS PAPER
Ventilation in Two Interconnected Rooms: Effects of the Exterior Vent Location and Size
R. Tovar,
R. Tovar
Universidad Nacional Auto´noma de Me´xico, Temixco, Mor., Me´xico
Search for other works by this author on:
C. A. Campo Garrido,
C. A. Campo Garrido
Universidad Nacional Auto´noma de Me´xico, Temixco, Mor., Me´xico
Search for other works by this author on:
P. F. Linden,
P. F. Linden
University of California at San Diego, La Jolla, CA
Search for other works by this author on:
L. P. Thomas
L. P. Thomas
Universidad Nacional del Centro, Tandil, Argentina
Search for other works by this author on:
R. Tovar
Universidad Nacional Auto´noma de Me´xico, Temixco, Mor., Me´xico
C. A. Campo Garrido
Universidad Nacional Auto´noma de Me´xico, Temixco, Mor., Me´xico
P. F. Linden
University of California at San Diego, La Jolla, CA
L. P. Thomas
Universidad Nacional del Centro, Tandil, Argentina
Paper No:
ANES/ASME2006-0004, pp. 5-10; 6 pages
Published Online:
August 14, 2008
Citation
Tovar, R, Campo Garrido, CA, Linden, PF, & Thomas, LP. "Ventilation in Two Interconnected Rooms: Effects of the Exterior Vent Location and Size." Proceedings of the ANES/ASME Solar Joint 2006 XXXth Mexican National Solar Energy Week Conference. ANES/ASME 2006 Joint XXXth National Solar Energy Week. Puerto de Veracruz, Mexico. October 2–6, 2006. pp. 5-10. ASME. https://doi.org/10.1115/ANES/ASME2006-0004
Download citation file:
4
Views
Related Proceedings Papers
Related Articles
Buoyancy-Driven Flow in Two Interconnected Rooms: Effects of the Exterior Vent Location and Size
J. Sol. Energy Eng (May,2009)
Fluid Flow and Heat Transfer in Rotating Curved Duct at High Rotation and Density Ratios
J. Turbomach (October,2005)
Combined Buoyancy and Pressure-Driven Flow Through a Shallow, Horizontal, Circular Vent
J. Heat Transfer (August,1995)
Related Chapters
Pulsating Supercavities: Occurrence and Behavior
Proceedings of the 10th International Symposium on Cavitation (CAV2018)
Handy Facts Regarding Types of Thermal Insulation
Hydraulics, Pipe Flow, Industrial HVAC & Utility Systems: Mister Mech Mentor, Vol. 1
Experimental Investigation of Ventilated Supercavitation Under Unsteady Conditions
Proceedings of the 10th International Symposium on Cavitation (CAV2018)